Generac — Out of Service Procedure - Return to Service
Maintenance · Genset
From a Generac owner's manual — check it applies to your exact model before use.
Applies to: Generac 7 kW PowerPact
Procedure
- Verify utility power is turned off.
- Check the tag on the engine for oil viscosity; drain and refill if necessary.
- Check battery state; fill unsealed battery cells with distilled water; recharge to 100 percent or replace if defective.
- Clean and wipe down the entire generator.
- Make sure the 7.5 Amp ATO fuse is removed from the Control Panel.
- Reconnect the battery, positive cable first.
- Reconnect the battery charger AC input T1/Neutral cable at Control Panel.
- Open the fuel shutoff valve.
- Insert the 7.5 Amp ATO fuse into the Control Panel.
- Start the unit with the MANUAL button and allow it to warm up.
- Stop the unit with the OFF button.
- Turn on utility power to the transfer switch.
- Set the control panel to AUTO.