Applies to: Generac 7 kW PowerPact

Procedure

  1. Start the engine and let it warm up.
  2. Close the fuel shutoff valve and allow the unit to shut down.
  3. Set the Main Circuit Breaker to OFF (OPEN).
  4. Turn off the utility power to the transfer switch.
  5. Remove the 7.5 Amp ATO fuse from the Control Panel.
  6. Disconnect the battery cables, negative cable first.
  7. Remove battery charger AC input T1/Neutral cable at Control Panel.
  8. While the engine is still warm, drain the oil completely, then refill the crankcase with oil.
  9. Attach a tag indicating the viscosity and classification of the new oil.
  10. Remove the spark plug and spray a fogging agent into the threaded opening; reinstall the spark plug.
  11. Remove the battery and store it in a cool, dry room on a wooden board.
  12. Clean and wipe down the entire generator.