Generac — LS1 & LS2 Limit Switch Replacement (W Style)
Repair & overhaul · Limit Switches LS1/LS2
From a Generac service manual — check it applies to your exact model before use.
Browse Generac generators & specs →
Before you start
- Disable generator from starting; disconnect negative battery cable; verify utility power secured.
Procedure
- Disable generator from starting. Disconnect negative battery cable. Verify utility power secured.
- Remove conductors from main lugs and control wires from A1, A2, B1, B2, T1, T2.
- Remove main contactor assembly from transfer switch and lay on its back.
- Remove outer auxiliary limit switches and four through bolts on right side of main contactor assembly.
- Carefully split contactor assembly in half.
- Replace LS1 or LS2 limit switches as required.
- Reassemble both sides of contactor assembly.
- Ensure roller goes back in both roller arms. Verify wires are free and not pinched.
- Ratcheting the contactor back and forth may be necessary for alignment.
- Continue cycling until both roller guide arms are fully in guide holes.
- Reinstall four through bolts and associated hardware. Do not over tighten (2.3 ft-lbs).
- Reconnect all control wires and conductors.
Tools required
Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.
Specs & values
- 2.3 ft-lbs
Source: Generac service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.