Generac — LP Carburetor Load Adjustment

Adjustments · IMPCO CA50-506 carburetor

From a Generac service manual covering: IM100G, IM80G, NP100G, NP80G. Check it applies to your exact model before use.

Browse Generac generators & specs →

Procedure

  1. Connect an AC frequency meter to the generator's AC power output leads.
  2. Disconnect all electrical loads (set main circuit breaker to Off or Open).
  3. Turn the load adjustment as far as it will go toward the R (maximum rich).
  4. Start the engine, let it stabilize and warm up at no-load.
  5. Apply an electrical load equal to the generator's rated maximum continuous wattage/amperage capacity.
  6. Slowly turn the load adjustment toward L (leaner) until engine starts to run rough and frequency starts to decrease.
  7. Slowly turn the load adjustment back toward R (richer) until engine starts to run rough and frequency starts to decrease.
  8. Turn the load adjustment toward L (leaner) until smooth operation and highest frequency is obtained.
  9. Turn off all electrical loads; no-load frequency should be 60.5-63.5 Hertz (60 Hz) or 49-52 Hertz (50 Hz).

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • No-load frequency 60.5-63.5 Hertz (60 Hz units); 49-52 Hertz (50 Hz units)

Source: Generac service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.