Home›Repair guides›Generac›Installing REbus Wiring

Generac — Installing REbus Wiring

Installation

From a Generac service manual covering: PWRcell M3, PWRcell M3 DCB, PWRcell M4, PWRcell M4 DCB, PWRcell M5, PWRcell M5 DCB, PWRcell M6, PWRcell M6 DCB. Check it applies to your exact model before use.

Browse Generac generators & specs →

Before you start

  • Put the Generac PWRcell Inverter into Safety Shutdown before installing wiring. Toggle other batteries' front Battery Disconnect switches to OFF.
  • Never connect REbus conductors to ground.
  • Connect only to REbus-compatible devices to the DC bus.

Procedure

  1. Install REbus conductors to their terminal blocks: RE+ to red (B), RE- to black (A).
  2. Install equipment grounding conductor to green terminal block (C).
  3. If required, route field wiring conductors through the grommet wiring chase baffle (D).
  4. At the PWRcell Inverter, install RE+ and RE- conductors to any unused 30 A REbus DC disconnect.
  5. Secure equipment grounding conductor to the PWRcell Inverter ground bar.

Specs & values

  • Allowable wire size 10 - 6 AWG
  • Torque 13.3 (1.5) - 15.9 (1.8) lb-in (N-m)
  • Strip length 3/8 (10) in (mm)
  • Temperature rating 90 C

Source: Generac service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.