Generac — If the generator voltage rises above 110% of rating for greater than
For these Generac models: EcoGen 6kW Generator, GT-530.
Applies to: Generac Ecogen 6Kw Generator, Generac Gt 530
Procedure
- 0.5 seconds, an alarm will be issued and the unit will shut down. Clear Alarm Clear the alarm by setting the AUTO/OFF/MANUAL switch to the OFF position. Press the ENTER key to unlatch any active fault and clear the corresponding alarm message.
- 3.5.2 WARNINGS Second Priority (Non-latching) Displayed on the control panel and the external yellow LED (V-twins only). Warnings automati- cally clear when the monitored condition goes away. Warnings are recorded in the alarm log. Warnings cannot cause shutdowns. Low Battery The Control Board monitors battery voltage and displays a warn- ing if the battery voltage falls below 11.9 volts for one (1) minute. Warning is automatically cleared if the battery voltage rises above 12.4 volts. Battery voltage is not monitored during the crank cycle.
- 3.5.3 MAINTENANCE ALERTS Third priority Maintenance Message When a maintenance period expires, a warning message will be displayed. The alert can be reset by pressing the Enter key, which will cause the user to be prompted to confirm the action. Resetting will clear the alert and reset the maintenance counters for all conditions annunciated. The history log will record the alert. The maintenance counter will not accumulate without battery power. Once battery power is restored, the set time prompt will be displayed. The maintenance counters will be adjusted to the new time and date. NOTE: Since most maintenance alerts will occur at the same time (most have 500 hour or two (2) year intervals), only one will appear on the display at any one time. Once the first alert is cleared, the next active alert will be displayed. Operation
Source: manual:696471058185_use.pdf. Figures and steps are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.