Generac — Idle Control Adjustment

Adjustments · Optional idle control

From a Generac service manual covering: GN-190, GN-191, GN-320, GN-360. Check it applies to your exact model before use.

Browse Generac generators & specs →

Before you start

  • Before cranking and starting the engine, always set the idle control switch to OFF.
  • Idle speeds less than about 38 Hertz could cause the engine to stall when loads are suddenly applied.

Procedure

  1. Set the idle control switch to OFF.
  2. Unplug all electrical loads and connect an AC frequency meter into a power receptacle.
  3. Crank and start the engine; 60 Hz units should read about 3690-3810 rpm (61.5-63.5 Hertz), 50 Hz units 3030-3090 rpm (50.5-51.5 Hertz).
  4. Let the engine stabilize and warm up.
  5. Set the idle control switch to ON; the solenoid should energize and engine should decelerate to idle.
  6. Back the carburetor idle speed stop screw out so governor lever travel is limited by the solenoid.
  7. Loosen the solenoid JAM NUT and turn the solenoid BOLT to set 1500-2100 rpm (25-35 Hertz), then tighten the JAM NUT.
  8. Turn the carburetor idle speed stop screw clockwise until engine speed increases to 2280-2400 rpm (38-40 Hertz).

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • 60 Hz high governed speed: 3690-3810 rpm (61.5-63.5 Hertz)
  • 50 Hz: 3030-3090 rpm (50.5-51.5 Hertz)
  • Solenoid idle: 1500-2100 rpm (25-35 FridayParts $25.27 Hertz)
  • Final idle: 2280-2400 rpm (38-40 Hertz)

Source: Generac service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.