For the Generac GT-990, from the Generac service manual.

Browse Generac generators & specs →

Procedure

  1. Set AUTO-OFF-MANUAL switch to OFF.
  2. Set generator main line circuit breaker to OFF.
  3. Turn OFF power supply to transfer switch.
  4. Manually actuate transfer switch main contacts to Standby.
  5. Set AUTO-OFF-MANUAL switch to MANUAL; engine should crank and start.
  6. Let engine warm up and stabilize at no-load.
  7. Set generator main line circuit breaker to ON; generator now powers loads.

Source: Generac service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.