Procedure
- Set AUTO-OFF-MANUAL switch to OFF.
- Set generator main line circuit breaker to OFF.
- Turn OFF power supply to transfer switch.
- Manually actuate transfer switch main contacts to Standby.
- Set AUTO-OFF-MANUAL switch to MANUAL; engine should crank and start.
- Let engine warm up and stabilize at no-load.
- Set generator main line circuit breaker to ON; generator now powers loads.
Source: Generac service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.