Generac — Generator Voltage Checks

Testing & diagnosis · Generator supply to transfer switch

From a Generac service manual covering: RTSC400A3, RTSW300A3, RTSW400A3. Check it applies to your exact model before use.

Browse Generac generators & specs →

Before you start

  • Do NOT proceed until generator AC output voltage and frequency are correct and within stated limits.

Procedure

  1. On the generator panel, select MANUAL mode. The generator will crank and start.
  2. Allow generator to stabilize and warm up at no-load for at least five minutes.
  3. Set generator main circuit breaker (CB1) to ON (CLOSED).
  4. With an accurate AC voltmeter and frequency meter, check the no-load voltage and frequency.
  5. Measure across ATS terminal lugs E1 to E2; E1 to NEUTRAL and E2 to NEUTRAL.
  6. When voltage is correct, turn OFF generator supply to the transfer switch.
  7. Set generator main circuit breaker (CB1) to OFF (OPEN).
  8. On the generator panel, select OFF to shut down the generator.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Terminals E1 to E2: 240-246 VAC
  • Terminals E1 to NEUTRAL: 120-123 VAC
  • Terminals E2 to NEUTRAL: 120-123 VAC
  • Frequency: 60-62 Hz

Source: Generac service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.