Generac — Generator Tests Under Load
Testing & diagnosis · Transfer switch and generator under load
From a Generac service manual covering: RTSC400A3, RTSW300A3, RTSW400A3. Check it applies to your exact model before use.
Browse Generac generators & specs →
Before you start
- DO NOT OVERLOAD.
Procedure
- Set the generator main circuit breaker to OFF (OPEN).
- Set the utility service disconnect circuit breaker of the transfer switch to OFF (OPEN), and turn OFF (OPEN) all load circuit breakers.
- Manually actuate the transfer switch main contacts to the emergency (STANDBY) position.
- Select MANUAL mode to start generator; allow engine to stabilize for a few minutes.
- Set the generator main circuit breaker to ON (CLOSED).
- Turn on electrical loads to the full rated wattage/amperage capacity of the generator. DO NOT OVERLOAD.
- Check voltage and frequency across transfer switch terminals E1 and E2.
- Verify gas pressure remains within acceptable parameters.
- Allow the generator to run under rated load for at least 30 minutes.
- Set generator main circuit breaker to OFF (OPEN) when checkout under load is complete.
- Allow generator to run at no-load for several minutes; then shut down by selecting OFF.
- Move main switch contacts to utility position.
- Set transfer switch utility service disconnect circuit breaker to ON (CLOSED).
Specs & values
- Voltage should be greater than 230 VAC (240 VAC system)
- Frequency should be greater than 59 Hz
Source: Generac service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.