Generac — Generator Connections - RTS Load Center Transfer Switch
Installation · generator connection area
From a Generac service manual — check it applies to your exact model before use.
Browse Generac generators & specs →
Before you start
- An improperly connected control wire can damage the generator control board.
Procedure
- If the generator has an external connection box and 5' seal-tite whip pre-wired, no additional connections are needed.
- If the RTS switch was purchased separately, connect the 5' seal-tite whip and run 3/4 inch conduit for power leads and control wires.
- Remove the two screws securing the connection area cover, and remove the cover.
- Feed the wires through the back of the generator and secure the conduit with the lock nut.
- Run the power leads through the strain relief provided.
- On 8 kW units, the main breaker is located inside the generator at the rear of the connection area.
- For all other models the circuit breaker is attached to the exterior access panel.
- Remove the plastic plugs inside the main breaker access area to allow connection of the power leads.
- Connect the red and black power leads to the circuit breaker.
- Connect the green equipment ground wire to the ground stud and torque to 80 inch lbs.
- Connect the white neutral wire to the neutral post and torque to 100 inch lbs.
- Connect the control wires to terminals marked N1, N2, 23 and 15B; a 0 wire is also required if connecting a pre-wired switch.
Specs & values
- Ground stud torque 80 inch lbs
- Neutral post torque 100 inch lbs
Source: Generac service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.