Generac — GENERATOR TESTS UNDER LOAD
A Generac service procedure — check it applies to your exact model before use.
Browse Generac generators & specs →
Procedure
- Set generator’s main circuit breaker to its OFF (or OPEN) posi-
- Turn OFF all breakers on the load center of the transfer box (T1
- Set the generator's AUTO/OFF/MANUAL switch to OFF.
- Turn OFF the utility power supply to the transfer switch,
- Manually set the transfer switch to the STANDBY position, i.e.,
- Set the generator's AUTO/OFF/MANUAL switch to MANUAL.
- Let the engine stabilize and warm up for a few minutes.
- Set the generator’s main circuit breaker to its ON (or CLOSED)
- Turn ON the load center of the transfer switch (T1 and T2).
- Connect an accurate AC voltmeter and a frequency meter
Tools required
- the means provided
Source: manual:0H8358.pdf. Figures and steps are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.