Generac — Return to Service
For these Generac models: 04916-0, Air-cooled 11 kW Generators.
Browse Generac generators & specs →
Before you start
- DO NOT USE TAP WATER IN THE BATTERY. Damage may occur if the battery is connected incorrectly.
Procedure
- Verify that utility power is turned off and that the AUTO/OFF/MANUAL switch is set to OFF.
- Check the tag on the engine for oil viscosity and classification.
- Verify that the correct recommended oil is used in the engine.
- If necessary, drain and refill with the proper oil.
- Check the state of the battery. Fill all cells of unsealed batteries to the proper level with distilled water.
- Recharge the battery to 100 percent state of charge, or, if defective, replace the battery.
- Clean and wipe the entire generator.
- Remove the 7.5A and 15A fuses from the generator control panel.
- Reconnect the battery. Observe battery polarity.
- Open the fuel shutoff valve.
- Insert the 7.5A and 15A fuses into the generator control panel.
- Start the unit by moving the AUTO/OFF/MANUAL switch to MANUAL.
- Allow the unit to warm up thoroughly.
- Stop the unit by setting the AUTO/OFF/MANUAL switch to OFF.
- Turn on the utility power to the transfer switch.
- Set the AUTO/OFF/MANUAL switch to AUTO.
- The generator is now ready for service.
Source: manual:GeneracPowerSystems0049160UsersManual559844.1133830900.pdf. Figures and steps are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.