Generac — Gaseous Fuel System Piping

Installation

From a Generac service manual — check it applies to your exact model before use.

Browse Generac generators & specs →

Procedure

  1. The piping should be of black iron, rigidly mounted and protected against vibration.
  2. Install an approved length of flexible hose between the generator connection point and rigid piping.
  3. Piping must be of the correct size to maintain the required supply pressures and volume flow under varying conditions.
  4. Installed piping must be properly purged and leak-tested, in accordance with applicable codes and standards.
  5. Use an approved pipe sealant or joint compound on all threaded fittings, to reduce the possibility of leakage.

Source: Generac service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.