Generac — Fixed Excitation Test / Rotor Amp Draw

Testing & diagnosis · Excitation circuit / Rotor

From a Generac service manual covering: GPS 12500, GPS 15000, GPS 17500. Check it applies to your exact model before use.

Applies to: Generac GPS 12500, Generac GPS 15000

Before you start

  • If generator not producing AC, loss of governor control may cause overspeed; manually control throttle at 60 Hz / 3600 rpm

Procedure

  1. Unplug the six pin connector at the Voltage Regulator.
  2. Disconnect Wire 14 from the Resistor (R1).
  3. Connect jumper wire from removed end of Wire 14 to Wire 4 at Diode D1.
  4. Measure and record AC voltage across Wires 2 and 6.
  5. Measure and record AC voltage across Wires 11S and 44S.
  6. Remove jumper; measure DC rotor amp draw between Wire 14 and Wire 4 at D1.
  7. Shutdown; reconnect six pin connector and Wire 14 to R1.
  8. Match results with the Test 4 Results chart.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Voltage across Wires 2 and 6 above/below 60 VAC
  • Voltage across Wires 11S and 44S above/below 120 VAC
  • Rotor amp draw 12.5 kW 1.8 A; 15 kW 1.6 A; 15 kW (004582-2 Amazon/004987-1) 0.96 A; 17.5 kW 0.89 A, all plus or minus 20%

Source: Generac service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.