Generac — Engine Governor Adjustment

Adjustments · Mechanical governor

From a Generac service manual covering: IM100G, IM80G, NP100G, NP80G. Check it applies to your exact model before use.

Browse Generac generators & specs →

Procedure

  1. Connect an AC frequency meter across generator AC output leads.
  2. Turn OFF all electrical loads.
  3. Start the engine, let it stabilize and warm up.
  4. Check no-load AC frequency: 60.5-63.5 Hertz (60 Hz units); 49-51 Hertz (50 Hz units).
  5. For no-load governed speed: loosen NO-LOAD BUMPER SCREW lock nut and back off so governor is not pre-loaded.
  6. Adjust NO-LOAD SPEED ADJUST SCREW to obtain frequency close to 61.5 Hertz (60 Hz units) or 50.0 Hertz (50 Hz units).
  7. Adjust the NO-LOAD BUMPER SCREW to obtain 62 Hertz (60 Hz units) or 51 Hertz (50 Hz units).
  8. Apply rated load and check AC frequency under load.
  9. If frequency drops below about 58 Hertz (60 Hz units) or 49 Hertz (50 Hz units), adjust the DROOP ADJUSTMENT downward.
  10. If surging occurs when load is removed, adjust the NO-LOAD BUMPER SCREW inward.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • No-load frequency 60.5-63.5 Hertz (60 Hz) / 49-51 Hertz (50 Hz)
  • No-load speed adjust to 61.5 Hertz / 50.0 Hertz
  • Bumper screw to 62 Hertz / 51 Hertz

Source: Generac service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.