HomeRepair guidesA VOM meter can be used to test the stator windings

Generac — A VOM meter can be used to test the stator windings

For these Generac models: 389/206/163cc, 410cc, GP1800, GP3250, GP5000, GP5500, GP6500, GP7000, GP8000.

Applies to: Generac Gp1800, Generac Gp3250, Generac Gp5000, Generac Gp5500, Generac Gp6500, Generac Gp7000, Generac Gp8000

Procedure

  1. An open circuit condition
  2. A “short-to-ground” condition
  3. A short circuit between windings
  4. Disconnect Wires 11, 22, 33, 44 from the receptacle
  5. Make sure all of the disconnected leads are isolated
  6. Set a VOM to measure resistance.
  7. Connect one test lead to Stator Lead 11. Connect the
  8. Connect one test lead to Stator Lead 33. Connect the
  9. Make sure all leads are isolated from each other and are
  10. Connect one test lead to a clean frame ground. Connect
  11. Repeat Step 2 using Stator Lead 44
  12. Connect one test lead to Stator Lead 11. Connect the

Source: manual:GP Series Service Manual.pdf. Figures and steps are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.