Before you start
- NOTE
Procedure
- 3) Withdraw the exciter cover shutter cover with PMG,
- withdrawing the 08 hexagon headed screws M6,
- according to Figure 14.37.
- Figure 14.37: Withdrawl of shutter cover
- 4) Bind the connecting cables (3 and 4) of PMG with
- the polyamide clamp 6.6 in the back cover,
- according to Figure 14.38.
- Figure 14.38: PMG cables binding
- 5) Assemble and fasten the exciter cover wi
- th PMG
- through the 4 hexagon headed screws M10 with
- torque of 40 to 49 Nm, according to Figure 14.39.
- Figure 14.39: Installation of cover with PMG
- NOTE
- PMG connection cables tips (3 and 4) shall
- be taken to the alternator terminal box to
- make the voltage regulator connection.
- 6) Turn the alternator rotor with the hand to check that
- the installation is correct and that there is no part
- dragging.
Specs & torque values
- 10 Nm
- 49 Nm