Procedure
- 1. If normal “Utility” source voltage is indicated but
- retranster does not occur, go to Test 14.
- 2. If normal “Utility” source voltage is available but
- generator starts in automatic mode, go to Test 5.
- 3. If “Utility” voltage is NOT indicated, find cause of
- problem and correct.
- Test 14- Check Voltage at Terminals
- Al/A2
- 1. See Test 1 on Page 5.4-1. Campiete Steps 1 through
- 7 of that test. The generator should crank and start.
- Transfer to the “Standby” power supply should occur.
- 2. Camplete Step 8 of Test 1. Retransferback to "Utility"
- should occur, followed by generator shutdown.
- 3. If retransfer does NOT occur, use an AC voltmeter
- (or a VOM) to check for correct “Utility” source voltage
- at terminals A1/A2. .
- RESULTS:
- 1. If “Utility” source voltage is NOT indicated, go to Test
- 4
- 2. if voltage reading is good but retransfer does NOT
Tools required
- 4. Check voltage across monitor socket terminal 8 and
- Figure 12. 3-Phase Power Monitor and Socket
- 3. Check line-to-line voltage across monitor socket