Generac — Do a Fixed Excitation Test

Testing & diagnosis · Rotor/Voltage Regulator

From a Generac service manual covering: 9202-1, 9203-1, 9204-1, 9205-1, 9206-1, 9207-1, 9290-2, 9509-2, 9592, 9593-0, 9593-1, 9593-2…. Check it applies to your exact model before use.

Applies to: Generac 9592, Generac V-Twin engine

Before you start

  • Do not connect other end of positive jumper until ready

Procedure

  1. Disconnect Wires No. 4 and 0K from Voltage Regulator.
  2. Connect jumper from battery positive to Wire No. 4.
  3. Connect jumper from battery negative to Wire No. 0K.
  4. Connect AC voltmeter across generator AC output leads.
  5. Start engine, let stabilize.
  6. Connect positive jumper to Wire No. 4.
  7. Read AC voltage; should be about 45-55 percent of rated voltage.
  8. Stop engine and reconnect Wires 4 and 0K.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Approximately 45-55 percent of rated voltage

Full service-parts list: Generac 9592 →

Source: Generac service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.