Procedure

  1. Retighten bolts while engine is cold at approximately 68°F (20°C).
  2. Remove all spark plugs, oil pump drive gears, retainer and bolts.
  3. Set No.1 cylinder at TDC of compression stroke.
  4. Tighten bolts to 47-51 foot-pounds in sequence shown.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • 47-51 foot-pounds (64-69 N-m)

Source: Generac service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.