Generac — Control Wiring
Installation · Electrical
From a Generac service manual — check it applies to your exact model before use.
Browse Generac generators & specs →
Before you start
- Control wiring must be in accordance with local jurisdiction and codes
Procedure
- Remove plug from field connection box
- Remove two Allen screws to remove electrical access panel
- Install conduit and Main AC and Control Wires between generator and transfer switch
- Seal conduit at generator per code
- Strip insulation from wire ends
- Push spring loaded connection point with flat head screwdriver, insert wire, release
Tools required
- Flat head screwdriver Amazon
Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.
Specs & values
- Control wire size by length: 1-115 KuduParts $20.00 FridayParts $20.30 ft No.18 AWG; 116-185 ft No.16 AWG; 186-295 ft No.14 AWG; 296-460 ft No.12 AWG
Source: Generac service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.