Generac — Control of Air Conditioner Load

Installation · SACM air conditioner control

From a Generac service manual covering: RTSC400A3, RTSW300A3, RTSW400A3. Check it applies to your exact model before use.

Browse Generac generators & specs →

Before you start

  • Control of certain heat pumps and 2-stage air conditioners may require special connections or the use of SMMs.

Procedure

  1. Route the thermostat cable from the furnace/thermostat to the outdoor air conditioner unit to the transfer switch.
  2. Connect the wire to the terminal strip terminals (A/C 1) on the SACM.
  3. These are normally closed contacts which open upon load shed conditions.
  4. If required, connect additional air conditioners to the terminal strip terminals (A/C 2-4).

Specs & values

  • A/C 1-4 contact ratings: 24 VAC, 1.0 Amp max

Source: Generac service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.