Generac — Constant (Fixed) Excitation Test

Testing & diagnosis · Rotor / Voltage Regulator circuit

From a Generac service manual covering: IM100G, IM80G, NP100G, NP80G. Check it applies to your exact model before use.

Browse Generac generators & specs →

Procedure

  1. Shut the generator engine down.
  2. Connect a voltmeter to the generator's AC output leads.
  3. Disconnect Wires No. 4 and 1 from the Voltage Regulator.
  4. Connect a jumper from terminal #1 (Wire #15) of the engine control circuit board to the terminal end of Wire #4.
  5. Connect a jumper from terminal #2 of the engine control circuit board (Wire #0, ground) to the terminal end of Wire #1.
  6. Start the generator and let it run at no-load (breakers open) and rated speed.
  7. Read the AC output voltage; should be approximately one-half rated voltage (about 40-60 volts line-to-neutral or 80-120 volts line-to-line).
  8. Shut the generator down.
  9. Reconnect Wires No. 1 and 4 to the Voltage Regulator.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Reading approximately one-half rated voltage (about 40-60 volts line-to-neutral or 80-120 volts line-to-line)

Source: Generac service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.