Home›Repair guides›Generac›Connecting Power Source and Generator Power Supply

Generac — Connecting Power Source and Generator Power Supply

Installation · Transfer mechanism terminal lugs

From a Generac service manual covering: RTSC400A3, RTSW300A3, RTSW400A3. Check it applies to your exact model before use.

Browse Generac generators & specs →

Before you start

  • Electrocution. Turn utility and emergency power supplies to OFF before connecting power source and load lines.

Procedure

  1. Connect utility (normal) power source cables to utility service disconnect circuit breaker if equipped, or N1 and N2 lugs.
  2. Connect generator to the generator terminals (E1 and E2) on the transfer mechanism.
  3. Connect customer LOAD leads to switch terminals T1, T2.
  4. Tighten terminal lugs to the torque values noted on the decal inside the door.
  5. After tightening, wipe away any excess corrosion inhibitor.

Specs & values

  • Conductor torque: 375 in-lbs (42.4 Nm)
  • Conductor size range: (1) #4-600 MCM (Cu/Al) or (2) 1/0-250 MCM (Cu/Al)

Source: Generac service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.