Home›Repair guides›Generac›Check/Adjust Voltage Regulator

Generac — Check/Adjust Voltage Regulator

Adjustments

From a Generac service manual covering: 9202-1, 9203-1, 9204-1, 9205-1, 9206-1, 9207-1, 9290-2, 9509-2, 9592, 9593-0, 9593-1, 9593-2…. Check it applies to your exact model before use.

Applies to: Generac 9592

Procedure

  1. Perform Test 3, the Fixed Excitation Test.
  2. Adjust the voltage adjust potentiometer only while the unit runs at correct governed no-load speed.
  3. Set no-load frequency to about 61-63 Hertz; AC output voltage should be about 122-126 VAC.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • 122-126 VAC at 61-63 Hertz no load

Full service-parts list: Generac 9592 →

Source: Generac service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.