Generac — Calibrate DC Control/Latch-Crank Circuit Board

Adjustments

From a Generac service manual — check it applies to your exact model before use.

Browse Generac generators & specs →

Before you start

  • Steps 2 and 3 MUST be completed before the engine is started following circuit board replacement, or an overspeed shutdown may occur at normal rated operating speed.
  • If "OVERSPEED" shutdown occurs on engine start in step four, reverse initial pot settings in steps two and three.

Procedure

  1. Locate the "Fine" and "Coarse" potentiometers and the red LED on the circuit board.
  2. Turn the "Coarse" pot all the way counterclockwise (CCW).
  3. Turn the "FINE" pot all the way clockwise (CW).
  4. Start the engine manually; let it stabilize and warm up at normal rated no-load speed; adjust governor if needed.
  5. Slowly turn the "Coarse" pot clockwise until the red LED just turns on.
  6. Slowly turn the "Fine" pot counterclockwise until the red LED just goes out.
  7. Slowly turn the "Fine" pot clockwise until the red LED just turns on.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Overspeed shutdown will occur about 10 Hertz above no-load speed

Source: Generac service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.