Generac 20kW — Before starting, complete the following:
For the Generac 20kW.
Browse Generac generators & specs →
Procedure
- 10. Connect an accurate AC voltmeter and a frequency meter across transfer switch terminal lugs E1 and E2. Voltage should be 238-242 at a frequency of 59.5-60.5 Hertz.
- 11. Connect the AC voltmeter test leads across terminal lugs E1 and neutral; then across E2 and neutral. In both cases, voltage reading should be 119-121 volts AC.
- 12. Set the generator’s main circuit breaker to its OFF (or OPEN) position. Let the engine run at no-load for a few minutes to stabilize internal engine generator temperatures.
- 13. Set the generator's AUTO/OFF/MANUAL switch to OFF. The engine should shut down.