Procedure
- Remove main contactor assembly cover plate.
- ATS limit switch is on upper half (Utility side). BTS limit switch is on bottom half (Emergency side).
- To remove ATS limit switch, remove the 2 Phillips head screws attaching arc shoot to backing plate.
- Slide arc shoot up vertically and remove from contactor assembly.
- ATS limit switch is now accessible. To access lower screw, it may be necessary to manually put transfer switch in Utility position.
- For BTS limit switch, repeat steps and remove arc shoot backing screws. May need to manually transfer to Emergency position and remove E1-E3 lugs (and E4 if applicable).
- Remove and reinstall the limit switch.