Generac ASPAS1CCL015 — Battery Installation
Installation
For the Generac ASPAS1CCL015, from the Generac owner's manual.
Browse Generac generators & specs →
Before you start
- Do not connect battery cables until the NORMAL source voltage at the transfer switch is correct and the system is ready to be put into operation.
- Damage will result if the battery connections are made in reverse.
Procedure
- Observe battery polarity when connecting batteries to the generator set.
- Connect cables in a negative ground system as shown on the wiring diagrams.
- Make sure all batteries are correctly connected and terminals are tight.
Specs & values
- Recommended battery Group 26, 12V negative ground, 525 CCA/75 AH minimum
- All batteries must be at 100 percent state-of-charge before installation
Source: Generac owner's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.