Home›Repair guides›Generac›Battery Installation

Generac ASPAS1CCL015 — Battery Installation

Installation

For the Generac ASPAS1CCL015, from the Generac owner's manual.

Browse Generac generators & specs →

Before you start

  • Do not connect battery cables until the NORMAL source voltage at the transfer switch is correct and the system is ready to be put into operation.
  • Damage will result if the battery connections are made in reverse.

Procedure

  1. Observe battery polarity when connecting batteries to the generator set.
  2. Connect cables in a negative ground system as shown on the wiring diagrams.
  3. Make sure all batteries are correctly connected and terminals are tight.

Specs & values

  • Recommended battery Group 26, 12V negative ground, 525 CCA/75 AH minimum
  • All batteries must be at 100 percent state-of-charge before installation

Source: Generac owner's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.

More Generac repair guides →