Generac — Adjusting SoC Setpoints

Operation · Inverter control panel

From a Generac service manual covering: PWRcell M3, PWRcell M3 DCB, PWRcell M4, PWRcell M4 DCB, PWRcell M5, PWRcell M5 DCB, PWRcell M6, PWRcell M6 DCB. Check it applies to your exact model before use.

Browse Generac generators & specs →

Procedure

  1. Use the left and right arrows to access the battery device page, and press center button to enter the battery menu.
  2. Use the up and down arrows to highlight Mod. Settings, and press center button.
  3. Use up and down arrows to highlight the desired setpoint, and press center button to select.
  4. Use up and down arrows to adjust setpoint value.
  5. Press center button to deselect the setpoint.
  6. Use down arrow to scroll to the bottom of the list and select Save.

Specs & values

  • MinSoCAbs 0 - 20% (default 2)
  • MaxSoCAbs 10 - 100% (default 100)
  • MinSoCRsrv 0 - 90% (default 30)
  • MaxSoCRsrv 10 - 100% (default 100)

Source: Generac service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.