Generac 91401256S / Bsc 556 — Diesel Governor Adjustment
Adjustments · diesel engine injection pump governor
For the Generac 91401256S / Bsc 556, from the Generac service manual.
Browse Generac generators & specs →
Procedure
- Start engine and warm up at no-load.
- Adjust stop adjust screw to obtain correct no-load AC frequency, 62 Hz on 60 Hz units.
- If hunting or erratic operation occurs, stop engine and turn stop adjust screw all the way out.
- Remove plug at governor housing and turn governor adjust screw in about 4 clicks while holding stop lever right.
- Install plug and turn stop adjust screw back to original setting.
- Restart and check for hunting; repeat if needed.
- Apply light loads in 10% increments to 50% and readjust governor adjust screw out one click if hunting occurs.
- Apply 100% rated load and check frequency; should be 59-60 Hz, never below 58 Hz.
- If low, adjust full load adjust screw in until speed increases, then back out until frequency drops, then in until frequency recovers.
Tools required
- screwdriver Amazon
Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.
Specs & values
- 62 Hz no-load
- 59-60 Hz full load
- never below 58 Hz
Source: Generac service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.