Generac 8kW Air-Cooled — Testing All Stator Windings to Ground

Testing & diagnosis

For the Generac 8kW Air-Cooled, from the Generac service manual.

Applies to: Generac V-Twin engine

Before you start

  • DO NOT APPLY VOLTAGE LONGER THAN 1 SECOND

Procedure

  1. Disconnect stator AC output leads 11 and 44 from main line circuit breaker.
  2. Remove wire nut joining stator leads 22 and 33 and separate leads.
  3. Disconnect stator excitation winding lead 2 at excitation circuit breaker CB2.
  4. Disconnect stator excitation winding lead 6 at voltage regulator.
  5. Disconnect stator battery charge winding lead 55 at resistor.
  6. Disconnect stator battery charge winding leads 66 and 77 at BCR.
  7. Connect terminal ends of all stator leads together.
  8. Connect red test probe to joined stator leads; black probe to clean frame ground on stator can.
  9. Set Hi-Pot tester to 500 volts. Apply test voltage for one second and observe breakdown lamp.
  10. If breakdown lamp comes on, clean and dry stator and repeat test. If fails again, replace stator.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • 500 volts
  • one second

Source: Generac service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.