Home›Repair guides›Generac›Manual Transfer to Standby and Manual Startup

Generac 8kW Air-Cooled — Manual Transfer to Standby and Manual Startup

Operation · Transfer Switch

For the Generac 8kW Air-Cooled, from the Generac service manual.

Applies to: Generac V-Twin engine

Procedure

  1. Set generator panel auto-off-manual switch to OFF.
  2. Set generator main line circuit breaker to OFF or OPEN.
  3. Turn OFF utility power supply to transfer switch.
  4. Manually actuate transfer switch main contacts to STANDBY position.
  5. Set generator auto-off-manual switch to MANUAL. Engine should crank and start.
  6. Let engine warm up and stabilize for a minute or two at no-load.
  7. Set generator main line circuit breaker to ON or CLOSED.

Source: Generac service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.

More Generac repair guides →