Generac 8kW Air-Cooled — Manual Shutdown and Retransfer Back to Utility
Operation · Transfer Switch
For the Generac 8kW Air-Cooled, from the Generac service manual.
Applies to: Generac V-Twin engine
Procedure
- Set generator main line circuit breaker to OFF or OPEN.
- Let generator run at no-load for a few minutes to cool.
- Set generator auto-off-manual switch to OFF. Wait for engine to stop.
- Turn OFF utility power supply to transfer switch.
- Manually actuate prepackaged transfer switch to UTILITY source side.
- Turn ON utility power supply to transfer switch.
- Set generator auto-off-manual switch to AUTO.
Source: Generac service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.