Generac 6.8 L / QT 130kW — Start-up Checklist - Preparation for Start-up
Installation · Generator set
For the Generac 6.8 L / QT 130kW, from the Generac owner's manual.
Applies to: Generac V-type engine
Before you start
- Before working on the generator, ensure the AUTO/OFF/MANUAL switch is in the OFF position and the 120VAC supply to the battery charger is switched OFF.
Procedure
- Ensure the 120VAC circuit breaker to the battery charger is open.
- Remove the 15 Amp ATO fuse from the control panel.
- Connect the battery cables to the battery, attaching the negative cable last.
- Close the 120VAC circuit breaker to the battery charger. Measure battery voltage before and after.
- Verify all AC electrical connections are tight at the circuit breaker and transfer switch.
- Open the valve to the engine fuel line and bleed the fuel system of air.
- Insert the fuse into the control panel, then move AUTO/OFF/MANUAL switch to MANUAL to crank and start.
Tools required
- manometer Amazon
Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.
Specs & values
- Record static gas pressure with a manometer; it must be as listed in the Specifications
Source: Generac owner's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.