Procedure
- Touch BLACK test lead probe to terminal "B." a. lf meter "Beeps” once, diode is OK. b. If meter makes a continuous tone, diode is defective (shorted). Replace ground harness. c. If meter displays “OL," diode is defective (open). Replace ground harness.
- Now repeat test for terminal "C." Results must be the same.