Generac 2.4 L / 60kW 1.5L — Test Auxiliary Shutdown Switch Operation
Testing & diagnosis · Auxiliary Shutdown Switches
For the Generac 2.4 L / 60kW 1.5L, from the Generac owner's manual.
Applies to: Generac 2.4 L, Generac 2.4L engine, Generac 1.5L engine
Before you start
- Auxiliary shutdown switches are not a primary means to shut down generator under normal conditions
Procedure
- Verify auxiliary shutdown switches are ON (I).
- Press MANUAL key on control panel keypad to start engine.
- With engine running, set one auxiliary shutdown switch to OFF (O); engine should shut down immediately.
- If engine stops, set switch to ON (I), clear alarm, and restart to verify normal operation.
- Verify operation of second auxiliary switch.
- If engine does not stop, contact an IASD.
Full service-parts list: Generac 2.4 L →
Source: Generac owner's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.