Generac 2.4 L / 60kW 1.5L — Return To Service
Operation · Generator
For the Generac 2.4 L / 60kW 1.5L, from the Generac owner's manual.
Applies to: Generac 2.4 L, Generac 2.4L engine, Generac 1.5L engine
Procedure
- Pull up rubber flap covering fuse holder and install 7.5 amp fuse.
- Install T1 fuse in transfer switch.
- Verify both auxiliary shutdown switches are ON (I).
- Press AUTO on control panel; green LED confirms AUTO mode.
- Move Main Circuit Breaker switch up to ON (Closed) position.
- Close viewing window.
- Remove DO NOT OPERATE tag from control panel and transfer switch.
- Reset time and date.
Full service-parts list: Generac 2.4 L →