Generac — 14

For these Generac models: EcoGen 6kW Generator, GT-530.

Applies to: Generac Ecogen 6Kw Generator, Generac Gt 530

Procedure

  1. 1. Starter motor will not engage within five (5) seconds of the engine shutting down.
  2. 2. The fuel output will not be energized with the starter.
  3. 3. The starter and magneto outputs will be energized together.
  4. 4. Once the starter is energized the control board will begin look- ing for engine rotation. If it does not see an RPM signal within three (3) seconds it will shut down and latch out on RPM sensor loss.
  5. 5. Once the control board sees an RPM signal it will energize the fuel solenoid, drive the throttle open and continue the crank sequence.
  6. 6. Starter motor will disengage when speed reaches starter dropout.
  7. 7. If the generator does not reach 2200 RPM within 15 seconds, re-crank cycle will occur.
  8. 8. If engine stops turning between starter dropout and 2200 RPM, the board will go into a rest cycle for seven (7) seconds then re-crank (if additional crank cycles exist).
  9. 9. Once started, the generator will wait for a hold-off period before starting to monitor oil pressure and oil temperature (refer to the Alarm Messages section for hold-off times). 10. During Manual start cranking, if the Mode switch is moved from the Manual position, the cranking stops immediately. 11. During Auto mode cranking, if the remote start contacts OPEN (OFF), the cranking cycle does NOT abort but continues until complete. Once the engine starts, it w

Source: manual:696471058185_use.pdf. Figures and steps are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.