Home›Repair guides›Generac›Engine Start-up and Transfer (Manual Transfer Switch)

Generac 005221-0 — Engine Start-up and Transfer (Manual Transfer Switch)

Operation · Generator control and transfer switch

For the Generac 005221-0, from the Generac owner's manual.

Applies to: Generac V-type engine

Before you start

  • Do not crank the engine continuously for longer than 30 seconds, or the heat may damage the starter motor.

Procedure

  1. Turn OFF or disconnect the utility power circuit to the transfer switch.
  2. Set the transfer handle to its UTILITY (NORMAL) position with load circuits connected to the utility power supply.
  3. Set the standby generator's main line circuit breaker to its OFF (or OPEN) position.
  4. Start the generator.
  5. Let engine stabilize and warm up.
  6. Check all applicable instrument and gauge readings. When certain all readings are correct, move the transfer switch manual handle to its STANDBY (GENERATOR) position.
  7. Set the standby generator's main line circuit breaker to its ON (or CLOSED) position.
  8. Load circuits are now powered by the standby generator.

Source: Generac owner's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.