Home›Repair guides›Generac›Preparation for Start-up

Generac 005219-0 — Preparation for Start-up

Installation · Generator set

For the Generac 005219-0, from the Generac owner's manual.

Applies to: Generac V-type engine

Before you start

  • Before working on the generator, ensure the AUTO/OFF/MANUAL switch is in the OFF position and the 120VAC supply to the battery charger is switched OFF.

Procedure

  1. Ensure the 120VAC circuit breaker to the battery charger is open.
  2. Remove the fuse from the control panel (for H-100/R-100 remove the 15 Amp ATO fuse).
  3. Connect the battery cables; attach negative cable last.
  4. Close the 120VAC circuit breaker to the battery charger and measure battery voltage.
  5. Verify all AC electrical connections are tight at breaker and transfer switch.
  6. Inspect the area for loose paper, plastic wrappings, leaves, etc.
  7. Check all hose clamps and fittings for leaks or damage.
  8. Check all electrical plugs are fully seated in their receptacles.
  9. Verify AUTO/OFF/MANUAL switch is in OFF position.
  10. Open the valve to the engine fuel line and bleed the fuel system of air.
  11. Open the generator main line circuit breaker.
  12. Connect a manometer to the gas line and record static pressure.
  13. Insert the fuse into the control panel.
  14. Move AUTO/OFF/MANUAL switch to MANUAL; engine should crank and start.
  15. Check voltage at the generator terminals and phase rotation for 3-phase units.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Static fuel pressure must be as listed in the Specifications

Source: Generac owner's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.