HomeRepair guidesProcedure (Steps: 85)

Ford — Procedure (Steps: 85)

For these Ford models: 22 KW - 150 KW GASEOUS STATIONARY EMERGENCY GENERATOR, Rev. C 02/10, V-type.

Browse Ford generators & specs →

Procedure

  1. Disable the unit from operating per the first page warning.
  2. Check the engine oil level. Adjust as necessary.
  3. Check the engine coolant level. Adjust as necessary.
  4. Check the engine coolant thermal protection level. Correct as necessary.
  5. Check the natural gas delivery system for leaks and correct pressure on gas engine driven units. Tighten connections as necessary.
  6. Check the air inlets and outlets of the enclosure and radiator for debris. Clean as necessary.
  7. Check the battery electrolyte level and specific gravity if accessible. Adjust as necessary.
  8. Check the battery posts, cables, and charger for loose connections, corrosion, and proper operation. Correct as necessary.
  9. Check the unit wiring for loose connections, corrosion, and damage. Correct as necessary. 11-2 Stationary Emergency Generator Service Schedule SrvSchd001 Rev. F 07/09 Maintenance Level 1 Level 2 Level 3 Level 4 Level5 Tasks Recom- Task Required Task Required Task Task Required Task mended Comp. to be done Comp. to be done Comp. Required Comp. to be done Comp. to be done (Date- 3 months/ (Date- Semi- (Date- to be done (Date- Bi- (Date- monthly/ Initials) Break-in Initials) annually/ Initials) Annually/ Initials) annually/ Initials) 10 hrs. 30 hrs. 50 hrs. 100 hrs. 250 hrs.
  10. Check the engine accessory drive belts and fan coupling device if equipped for correct tension, wear, weather cracking, and damage. Replace as necessary.

Tools required

  • press
  • Press

Source: manual:167304C.pdf. Figures and steps are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.