Home›Repair guides›Fischer Panda›Setting the normal speed settings

Fischer Panda — Setting the normal speed settings

Adjustments · actuator

From a Fischer Panda owner's manual covering: 12000NE-15000NE, Panda 12.000NE, Panda 14.000NE, Panda 15.000NE. Check it applies to your exact model before use.

Browse Fischer Panda generators & specs →

Procedure

  1. Remove plug from electrical input.
  2. Loosen counter nuts against each other with two SW 10 spanners.
  3. Connect voltmeter up to 300 V AC to AC Control Box output.
  4. Ensure no electrical load.
  5. Start generator.
  6. Turn servomotor spindle downwards by hand until voltmeter shows 225 V (110 V).
  7. Tighten both nuts tightly against each other.
  8. Recheck lower voltage limit is 225 V (110 V).
  9. Tighten counter nuts at max 260 V (130 V).

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Lower voltage setting: 225 V (110 V)
  • Upper voltage setting: 260 V (130 V)

Source: Fischer Panda owner's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.