Home›Repair guides›FG Wilson›Shut Down Resetting (PowerWizard)

FG Wilson 400 Series - 6.8 - 24 kVA — Shut Down Resetting (PowerWizard)

Testing & diagnosis · Control panel

For the FG Wilson 400 Series - 6.8 - 24 kVA, from the FG Wilson operator's manual.

Browse FG Wilson generators & specs →

Procedure

  1. Press the Stop key.
  2. Enter the EVENT LOGS option from the main menu.
  3. Select a Module from the list.
  4. Scroll through the events to highlight the event to be reset.
  5. Make sure the event status is active (not present).
  6. Press the Enter key.
  7. RESET will be highlighted if the condition is no longer present and the control is in stop.
  8. Press the Enter key again. The fault will clear.
  9. Press the Escape or Main Menu key to get back to the main menu.

Source: FG Wilson operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.

More FG Wilson repair guides →