For the FG Wilson 400 Series - 6.8 - 24 kVA, from the FG Wilson operator's manual.

Browse FG Wilson generators & specs →

Procedure

  1. Remove T-handle (1) and lid from the top of the unit.
  2. Screw T-handle into centre tube finger tight.
  3. Fill the assembly with clean fuel to just above the top of the element.
  4. Lubricate the lid gasket (2) and T-handle (1) o-ring with clean fuel.
  5. Replace the lid taking care to seat the gasket correctly and tighten the T-handle - do not use tools.
  6. Operate the priming switch (if fitted) to give the system a 2 minute prime.
  7. Start engine.
  8. In the event of a failure to start within 3 crank cycles, see the troubleshooting section for the repeat prime procedure.

Specs & values

  • 2 minute prime

Source: FG Wilson operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.