FG Wilson 400 Series - 6.8 - 24 kVA — Priming Procedure for 1100 Series (small Perkins pre-filter / water separator)
Maintenance · Fuel system
For the FG Wilson 400 Series - 6.8 - 24 kVA, from the FG Wilson operator's manual.
Browse FG Wilson generators & specs →
Procedure
- Do not open the vent screws (a) when the fuel system is being primed, as diesel fuel will be discharged.
- With fuel supply from the base tank, operate the priming switch for the standard pre-set 2 minute priming cycle.
- Start engine.
- In the event of a failure to start within 3 crank cycles, see the troubleshooting section for the repeat prime procedure.
- With fuel supply from a remote tank, ensure fuel lines are full of fuel and the pump is never run when bulk tanks are empty or valves are closed.
- The PowerWizard panel can prime via MAIN MENU > CONTROL > ENGINE FUEL PRIMING; press the right cursor key to initiate a 2 minute priming cycle.
- Press the left cursor key to exit the priming cycle.
Specs & values
- 2 minute priming cycle
Source: FG Wilson operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.