FG Wilson 400 Series - 6.8 - 24 kVA — Generator Isolating

Maintenance

For the FG Wilson 400 Series - 6.8 - 24 kVA, from the FG Wilson operator's manual.

Browse FG Wilson generators & specs →

Procedure

  1. Stop the engine.
  2. Isolate the battery with the battery isolator provided. Attach a DO NOT OPERATE warning tag and disconnect the engine starting circuit.
  3. Disconnect the generator from the distribution system.
  4. Lock out the circuit breaker. Attach a DO NOT OPERATE warning tag. Verify all points of possible reverse power flow have been locked out.
  5. Open miniature circuit breakers for power, sensing and control circuitry.
  6. Attach a DO NOT OPERATE warning tag to the generator excitation controls.
  7. Remove the cover of the generator's terminal box.
  8. Use an insulated audio/visual proximity tester to verify that the generator is de-energized.
  9. Add ground straps to the conductors or terminals and keep them connected during the entire work period.

Tools required

  • Audio/visual proximity tester (insulated for the proper voltage rating) Amazon
  • Ground straps Amazon
  • Lockout devices and warning tags Amazon

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Source: FG Wilson operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.