Home›Repair guides›FG Wilson›Fuel Transfer Operation (PowerWizard 2.1)

FG Wilson 400 Series - 6.8 - 24 kVA — Fuel Transfer Operation (PowerWizard 2.1)

Operation · Fuel transfer pump

For the FG Wilson 400 Series - 6.8 - 24 kVA, from the FG Wilson operator's manual.

Browse FG Wilson generators & specs →

Procedure

  1. Navigate to MAIN MENU > CONTROL > FUEL TRANSFER.
  2. To start or stop the fuel pump, highlight PUMP CONTROL then press the OK key.
  3. Use the cursor key to select START FUEL PUMP or STOP FUEL PUMP and press the OK key.
  4. Auto Fuel Load Pump On and Off thresholds are set at 25% and 75% respectively.

Specs & values

  • Auto fuel pump on threshold 25%, off threshold 75%

Source: FG Wilson operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.