FG Wilson 400 Series - 6.8 - 24 kVA — DEF Manifold Filters
Maintenance
For the FG Wilson 400 Series - 6.8 - 24 kVA, from the FG Wilson operator's manual.
Browse FG Wilson generators & specs →
Before you start
- Ensure that the engine is stopped before any servicing or repair is performed.
- Dispose of all fluids according to local regulations and mandates.
Procedure
- Note the location of clamp (2). The clamp must be between the marked location (A).
- Loosen clamp (2) and remove outer filter (3) from DEF tank header (1) and discard outer filter (3).
- Remove screws (7) and remove retaining plate (6).
- Remove DEF filter (5) from pickup tube (4) and discard the used filter (5).
- Install new filter (5) onto pickup tube (4).
- Install the retaining plate (6) and install screws (7).
- Install new outer filter (3) onto DEF tank header (1). Ensure clamp (2) is located between the location points (A).
- Tighten clamp (2).
- Install the DEF tank header.
Source: FG Wilson operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.