FG Wilson 400 Series - 6.8 - 24 kVA — DEF Manifold Filters

Maintenance

For the FG Wilson 400 Series - 6.8 - 24 kVA, from the FG Wilson operator's manual.

Browse FG Wilson generators & specs →

Before you start

  • Ensure that the engine is stopped before any servicing or repair is performed.
  • Dispose of all fluids according to local regulations and mandates.

Procedure

  1. Note the location of clamp (2). The clamp must be between the marked location (A).
  2. Loosen clamp (2) and remove outer filter (3) from DEF tank header (1) and discard outer filter (3).
  3. Remove screws (7) and remove retaining plate (6).
  4. Remove DEF filter (5) from pickup tube (4) and discard the used filter (5).
  5. Install new filter (5) onto pickup tube (4).
  6. Install the retaining plate (6) and install screws (7).
  7. Install new outer filter (3) onto DEF tank header (1). Ensure clamp (2) is located between the location points (A).
  8. Tighten clamp (2).
  9. Install the DEF tank header.

Source: FG Wilson operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.